Island Mode.
Can your critical operations keep running when the link to IT is cut?
If the link between IT and OT were cut tonight, could your operation run as an island? For most operators, not yet. This 19-page e-book shows why, who has to own it, and a phased path that starts with what you already own.
Free. Fill in a short form and the download opens straight away. We also email you the link.
Incident response is half the answer
Recent incidents share a pattern. Where operations kept going, people could run them by hand. Where operations stopped without physical damage, a business system was usually the reason. Incident response decides who detects, contains and reports. Island mode decides what the operation does while that happens.
Colonial Pipeline
Ransomware reached the corporate network and the billing system. The pipeline was halted as a precaution, although the control network was not infected.
Nova Scotia Power
Ransomware cut the utility off from its customer meters. The grid stayed up, but about half of customers' bills were estimated for close to a year.
Jaguar Land Rover
An attack on IT systems halted manufacturing worldwide. UK production was suspended for about five weeks.
What island mode means
Island mode is a planned operating state. Vital OT and the systems it needs run with no connection to IT, cloud, the internet or third parties, and still deliver the service. It is entered on a trigger and left on agreed criteria.
It is not a permanent air gap. In normal operation, governed connections stay in place.
The allied CI Fortify guidance, published in July 2026, asks operators to aim to isolate vital OT and the systems it depends on from all other networks for three months while maintaining critical services. Most plans start by proving days, then weeks.
Graduated isolation
- Remote-worker access cutJump-host access for remote staff is disabled.
- On-site remote access cutOn-premises remote access into OT is disabled.
- All IT links cutEvery connection between OT and non-OT networks is isolated.
- Peer OT links cutLower-priority links between OT sites are isolated.
- Full islandVital OT runs alone and still delivers the service.
The cable test: nine ties that keep OT tied to IT
Cut the cable tonight and the controllers keep running their loops. But operators can lose their view and command, and the plant record can stop, because in many plants nine things still tie OT to IT.
T1Shared virtual servers
Operator stations, servers and the historian run on virtualization that IT manages.
Check: map each OT virtual server to its host, storage and backup.
T2Routing through IT
The control network's default route points to the IT core.
Check: read the OT firewalls' routing tables end to end.
T3OT on the IT edge
Remote sites and vendor links end on IT edge firewalls, with no broker.
Check: list every tunnel and VPN group that lands in OT.
T4Shared switching
One spanning-tree domain crosses IT and OT, so an IT-side change reshapes the OT network.
Check: find the root bridge of each OT switch domain.
T5Shared identity
OT logons depend on a domain, trusts or controllers that IT runs.
Check: list the domain controllers and trusts OT relies on.
T6Time from outside
OT clocks follow corporate or internet time servers, not a local source.
Check: trace every OT time source to its origin.
T7Shared management
One management network or console spans IT and OT systems.
Check: see who can reach hypervisor and switch management.
T8Internet and vendor clouds
OT segments reach, or try to reach, the internet; some vendor functions may need a cloud.
Check: review outbound denies; ask vendors in writing.
T9Untested recovery
No tested OT restore, and no agreed recovery time or recovery point.
Check: time a full restore of one critical server.
Where do you stand?
Boards need one honest answer to "how ready are we?" Five levels give it, and each rests on evidence rather than opinion. We often find operators at level 0 or 1. Ninety days is enough to reach level 2 and put a date on the first live test.
Assumed
"Isolate if required" is written down. Nobody has tested what it breaks.
Mapped
Vital systems, service targets, paths and dependencies are documented.
Rehearsed
A graduated plan and decision rights have been walked by all four seats.
Proven
Partial isolation tested in a maintenance window; manual procedures exercised.
Sustained
Full isolation tested on a schedule; paths reviewed quarterly for drift.
A path that starts with what you already own
Island mode is designed and owned jointly by IT, OT, operations and the business. It is proven by testing, not by diagrams.
Ownership, before all
Shared platforms serve both IT and OT and answer to neither. Name an owner for OT cyber risk, each shared platform and every isolation step.
Return on what you own
Hardened firewalls, a corporate PAM, managed switches and earlier designs often cover much of the next step. Configure first; buy only what closes a gap.
PAM first, then the OT door
One remote-access route with two gates. IT owns who; OT owns where and when. In island mode, remote access closes.
Two walls, one island
OT walls make each plant self-sufficient. IT walls keep an IT incident away from the platforms OT still shares, until they are split.
Ownership first. Then configure what you own, close the ties one by one, and prove the island with a test.
Get the Island Mode e-book
- Part 1
- What happened. 2026 in one page, and why the plant can run while the business stops.
- Part 2
- Where most operators stand. Island mode, the cable test, three paths in, the isolation clock and insurance.
- Part 3
- What to do. Ownership, four seats, ten priorities, remote access, segmentation and an 18-month path.
- Part 4
- Start. A twelve-question readiness check and a first working session.
Written for
- Executives and boards of power, water and other critical infrastructure operators
- CISOs, OT security leads and IT leaders who share the boundary
- Operations and engineering leaders who would run the plant by hand
- Risk, insurance and regulatory leads who answer for continuity
Your copy, straight away
Enter your name and business email. The download opens as soon as you submit, and we email you the link for later.
By requesting the e-book, you ask InnovAKT to send you its download link. We use your details to fulfil this request, and you can unsubscribe from our emails at any time. Privacy Policy.
Form not loading? Open the secure request form.
Start with one working session
Ninety minutes with four seats at the table: IT, OT, operations and the business. We bring the cable test, a draft isolation clock and the readiness check. Everyone leaves with named owners, a first dependency map and a 90-day plan.
Questions leaders ask
What is island mode?
A planned operating state in which vital OT and the systems it depends on run with no connection to IT, cloud, the internet or third parties, while still delivering the critical service at a defined level. It is entered on a trigger and left on agreed criteria.
Is island mode the same as an air gap?
No. An air gap is permanent. Island mode is a state you enter when needed and leave on agreed criteria. In normal operation, governed connections between IT and OT stay in place.
How long should we be able to run isolated?
The allied CI Fortify guidance sets a benchmark of three months. Most organizations start by proving days, then weeks, because a long isolation exposes every hidden dependency, including people, fuel, chemicals and spares.
Where do we start?
With ownership. Name who owns OT cyber risk, the shared platforms and each isolation step. Then map the ties between IT and OT, walk the isolation plan on paper with all four seats, and set a date for the first test in a maintenance window.
Go deeper
- No Mainland to Call, book one of The OT CISO series: cybersecurity and resilience for islands and isolated critical infrastructure.
- The Island Operator's Guide, free from InnovAKT.
- CI Fortify: advice for isolating vital systems, from the Australian Signals Directorate and partner agencies.
Sources for the incidents above: Jalopnik, citing CNN (Colonial Pipeline); Global News (Nova Scotia Power); Cyber Monitoring Centre (Jaguar Land Rover). The full source list is in the e-book.